Indoor Air Quality Monitoring for Homes, Schools, and Offices
Indoor air quality has a direct impact on health, comfort, and cognitive performance. IAQ Controls designs indoor air quality monitors that measure key environmental factors including carbon dioxide (CO₂), volatile organic compounds (VOCs), particulate matter (PM2.5), temperature, and humidity. By tracking these metrics in real time, homeowners, teachers, and facility managers can identify poor ventilation, airborne pollutants, and unhealthy indoor conditions before they become a problem.
Our IAQ monitors are built to help you understand what is happening in your indoor environment and why it matters. Elevated CO₂ levels can indicate insufficient fresh air, while high PM2.5 and VOC concentrations are commonly linked to respiratory irritation, fatigue, and reduced focus. Continuous indoor air quality monitoring provides actionable data to improve ventilation strategies, optimize HVAC performance, and create healthier indoor spaces.
ACCURACY SPECIFICATIONS
Understanding the accuracy of your air quality sensors is essential because low grade or estimated e CO₂ readings often give misleading results. Accurate NDIR based measurement ensures you know the true CO₂ levels in your home, office, or classroom.
CO2 ACCURACY
Measuring Range: 0-5000PPM
Sensor Type: Non-Dispersive Infrared
Accuracy: (0~3000PPM) +/- 50ppm or 5% of reading
Accuracy: (>3000PPM) +/- 7% of reading
Temp Compensation: +/- 0.1% of Reading per degree Celsius or
+/- 2PPM per degree Celsius.
Repeatability: 20PPM at 400PPM
Response Time: 2min for 63% of step change or < 4.6min
for 90% step change
Warm Up Time: <20 seconds
TEMPERATURE
Temperature Sensor
Operating temperature: 32°F ~ 195°F (0°C ~90°C)
Display resolution: 0.1°F (0.1°C)
Response time: <20 minutes (63%)
HUMIDITY
Measuring range: 5~95%
Accuracy: ±5%
Display resolution: 1% Main interface display, 0.1% Max/Min display